Troubleshooting

IED does not connect

Check these items first:

  • IP address is correct.
  • MMS port is correct, usually 102.
  • PC and IED are in the same routed network.
  • Windows firewall allows ARServer outbound access and Modbus inbound access when used.
  • IED MMS service is enabled.
  • Another engineering tool is not exhausting available client sessions.
  • VLAN, gateway, subnet mask, and switch port are correct.

Discovery connects but returns few or no signals

Possible causes:

  • The IED restricts online model browsing.
  • The selected access point is not the MMS access point.
  • The IED model exposes object names in a vendor-specific shape.
  • The relay allows reading known objects but limits directory browsing.

Recommended action:

  • Try Open SCL/CID/SCD if available.
  • Check diagnostics for domain and variable browse messages.
  • Probe a known CB position or measurement from SCL.

Probe selected fails

Probe validates the final object path and functional constraint. Failure may mean:

  • object path differs from the discovered candidate,
  • functional constraint is wrong,
  • the relay does not allow the attribute read,
  • the point is not present in this IED variant,
  • the connection was closed by the IED after a malformed or unsupported request.

Try another candidate from the same logical node, or use SCL import for more deterministic object references.

Value is live but timestamp is blank

The value attribute may be readable while the companion t timestamp attribute is not present or not allowed. ARServer leaves timestamp blank rather than generating a device timestamp.

Value is live but quality is blank or Bad

Quality comes from the companion q attribute when available. If the relay returns an invalid or unavailable quality, ARServer shows that state.

Modbus client connects but values do not change

Check:

  • Runtime is running.
  • The IEC value is live in the runtime grid.
  • The binding is enabled.
  • The Modbus register address is correct.
  • The client uses the correct Unit ID.
  • The client uses the same zero-based or one-based address convention as your mapping.
  • The client reads the correct data type size.

MQTT publishes nothing

Check:

  • MQTT is enabled globally.
  • MQTT is enabled for the selected binding.
  • Broker host and port are correct.
  • Broker accepts anonymous or configured credentials.
  • Network/firewall allows broker access.
  • Diagnostics tab shows MQTT connected.

Runtime is blocked

ARServer blocks runtime when it cannot create a safe live IEC session. This avoids publishing stale or invented values.

Fix the IEC connection first, then start runtime again.

When to use SCL import

Use SCL/CID/SCD/ICD when:

  • IP discovery returns too many candidates,
  • online browse is restricted,
  • you need DataSet or RCB planning,
  • you want a repeatable engineered mapping,
  • the relay object structure is known from the project file.

What information to include in a bug report

Include:

  • ARServer version,
  • Windows version,
  • relay vendor/model/firmware when shareable,
  • whether the workflow used Add by IP or Open SCL,
  • screenshot of diagnostics,
  • selected IEC object,
  • expected value and observed value,
  • Modbus/MQTT settings if the issue is output-related.